System Security

The system prevents unauthorized access into the process control and prevents unauthorized software or data changes.

Application Security

The system gives you the ability to control access to the system:

  1. User authentication

    1. Minimum user name and password based authentication

    2. Password complexity enforcement

    3. Password expiry

    4. User lock-out for incorrectly entering password a set number of times during login.

  2. Electronic Records

    1. Only authorized personnel can access data

    2. All data changes will be logged

  3. Irrefutability

    1. Where applicable Electronic data will be associated with their approver in an irrefutable manner

  4. Privileges

    1. Access to various system functions will be controlled via user role membership

User Privileges

Various roles are assigned to specific system functions as per the table below.

A set of roles may be combined in a group and then that group can be assigned to a user.

For more information on groups and roles, see section Group Management Form.

The following roles are available:

System Function of Assigned Roles

System Function

Assigned Role

Document Section Reference

Access PLC Configuration

Administrator

PLC Configuration

Acknowledge an alarm

Alarms Manager

User Interfaces

Clear an alarm (Force Clear)

Alarms Manager

User Interfaces

View Current and Historical Alarms

Alarms Manager

User Interfaces

Calibrate EO-type sensor while chamber is running a cycle

Calibrate EO While Running

Performing Calibration

Sign calibration certificate as “Performed By”

Calibration Performer

Manual

Enter new “Adjust” and “Notify” tolerances during calibration

Calibration Tolerances Manager

Manual

Specify expiry date for calibration session

Calibration Tolerances Manager

Calibration Performer

Calibrations Manager

Manual

Calibrate a sensor

Calibrations Manager

Calibration Module

Capture or set “Reading” value during calibration

Calibrations Manager

Manual

Reset calibration for individual devices

Calibrations Manager

Manual

Manually enter “As Found” and “As Left” values during calibration

Calibrations Manager

Manual

Configure charts

Chart Administrator

User Interfaces

View charts

Chart Viewer

User Interfaces

Click Set button for Chamber Conditions and Process Indicators (on Chamber P&ID and Dashboard)

Cycle Adjuster

User Interfaces

Approve Cycle Definition

Cycle Definition Approver

Super-Atmospheric EO Dwell

Create cycle definitions

Cycle Definition Creator

Super-Atmospheric EO Dwell

Revise existing cycle definitions

Cycle Definition Creator

Super-Atmospheric EO Dwell

View cycle definitions

Cycle Definition Viewer

Super-Atmospheric EO Dwell

Database management

Database Administrator

Database Maintenance

Import or delete imported DataTrace data into AccuSOLO database

DataTrace Manager

Interlocks

Reset maintenance timers

Device Maintenance Technician

Device Diagnostics and Manual Control

Manage drums

Drum Administrator

Drum Database Management

Set Maximum gross weight allowed before EO tank is considered to be on the scale

Drum Administrator

Miscellaneous General Configuration Parameters

Set Minimum gross weight that EO tank must be in order to be accepted

Drum Administrator

Miscellaneous General Configuration Parameters

Set Weigh scale wait duration [Parameter 1005]

Drum Administrator

Miscellaneous General Configuration Parameters

Set Stagnant weight delay

Drum Administrator

Miscellaneous General Configuration Parameters

Remove drum

Drum Handler

Drum Removal

Assign drum to chamber

Drum Handler

Drum Assignment

Edit a process run (cannot edit the customer or spec identity if the run is past the non-proc stage)

Edit Loads

Editing Loads

Modify PLC event configuration

Edit PLC Event

Events Module

Change chamber temperature set-point during a cycle

General Configuration Administrator

Manual Overrides

Change jacket temperature set-point during a cycle

General Configuration Administrator

Manual Overrides

Change minimum/maximum jacket temperature alarm tolerance during a cycle

General Configuration Administrator

Manual Overrides

Change duration set-point during supported phases

General Configuration Administrator

Manual Overrides

Change loop count set-point during supported phases

General Configuration Administrator

Manual Overrides

Change pressure set-point during supported phases

General Configuration Administrator

Manual Overrides

Set chamber temperature warning offset

General Configuration Administrator

Chamber Temperature

Set jacket temperature warning offset

General Configuration Administrator

Jacket Temperature

Set product temperature warning offset

General Configuration Administrator

Product Temperature

Set pressure warning offset

General Configuration Administrator

Pressure

Set relative humidity warning offset (section Relative and Absolute Humidity)

General Configuration Administrator

Relative and Absolute Humidity

Set absolute humidity warning offset

General Configuration Administrator

Relative and Absolute Humidity

Set EO concentration warning offset

General Configuration Administrator

EO Concentration

Set chamber temperature hysteresis tolerance

General Configuration Administrator

Chamber Temperature

Set jacket temperature hysteresis tolerance

General Configuration Administrator

Jacket Temperature

Set product temperature hysteresis tolerance

General Configuration Administrator

Product Temperature

Set pressure hysteresis tolerance

General Configuration Administrator

Pressure

Set relative humidity hysteresis tolerance

General Configuration Administrator

Hysteresis Tolerance Parameters and Warning Alarms

Set absolute humidity hysteresis tolerance

General Configuration Administrator

Hysteresis Tolerance Parameters and Warning Alarms

Set EO concentration hysteresis tolerance

General Configuration Administrator

EO Concentration

Set time delay for chamber temperature alarm

General Configuration Administrator

Time Delay for Chamber/Product Temperature Alarm

Set time delay for inject temperature alarm

General Configuration Administrator

Time Delay for Inject Temperature Alarm

Set end of phase dwell duration

General Configuration Administrator

End of Phase Dwell Durations

Set minimum chamber temperature offset for phase end

General Configuration Administrator

Chamber Temperature and Product Temperature

Set minimum product temperature offset for phase end

General Configuration Administrator

Chamber Temperature and Product Temperature

Set minimum/maximum pressure offset for phase end

General Configuration Administrator

Pressure

Set minimum relative humidity offset for phase end

General Configuration Administrator

Relative/Absolute Humidity

Set minimum absolute humidity offset for phase end

General Configuration Administrator

Relative/Absolute Humidity

Set minimum EO concentration offset for phase end

General Configuration Administrator

EO Concentration

Set the RH/AH control differential

General Configuration Administrator

Chamber Configuration (Equipment/Phase Config)

Set N2 inject temperature min/max alarm tolerance

General Configuration Administrator

Chamber Configuration (Equipment/Phase Config)

Set steam inject temperature min/max alarm tolerance

General Configuration Administrator

Chamber Configuration (Equipment/Phase Config)

Set EO inject temperature min/max alarm tolerance

General Configuration Administrator

Chamber Configuration (Equipment/Phase Config)

Set condensation warning offset

General Configuration Administrator

Cycle Execution Options

Enable condensation warning

General Configuration Administrator

Cycle Execution Options

Set Exhaust/vacuum switchover value

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set Normal anti-cavitation pressure

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set First EO evacuation anti-cavitation pressure

General Configuration Administrator

Chamber Configuration (Equipment/Phase Config)

Set Maximum pressure for paddle switch

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set Dormant temperature offset

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set Pressure ramp hold under offset

General Configuration Administrator

Ramp-Hold Time Parameters

Set Pressure ramp hold over offset

General Configuration Administrator

Ramp-Hold Time Parameters

Set Pressure ramp unhold under offset

General Configuration Administrator

Ramp-Hold Time Parameters

Set Pressure ramp unhold over offset

General Configuration Administrator

Ramp-Hold Time Parameters

Set ramp hold time 1

General Configuration Administrator

Ramp-Hold Time Parameters

Set ramp hold time 2

General Configuration Administrator

Ramp-Hold Time Parameters

Set ramp hold time 3

General Configuration Administrator

Ramp-Hold Time Parameters

Set ramp hold time 4

General Configuration Administrator

Ramp-Hold Time Parameters

Set ramp hold split limit

General Configuration Administrator

Ramp-Hold Time Parameters

Set Maximum duration for general failure

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set Number of product temperatures

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set Approximate altitude

General Configuration Administrator

Miscellaneous General Configuration Parameters

Set duration between run record inserts

General Configuration Administrator

Run Record Inserts

Enable blower alarm

General Configuration Administrator

Cycle Execution Options

Enable general failure

General Configuration Administrator

NA

Enable hold for low/high product temperature

General Configuration Administrator

Cycle Execution Options

Enable User Hold

General Configuration Administrator

Cycle Execution Options

Set high concentration end limit

General Configuration Administrator

Process

Set Leak Check pressure control offset

General Configuration Administrator

Leak Check

Set Continuous Steam Conditioning pressure control offset

General Configuration Administrator

Continuous Steam Conditioning

Set Air In-bleed pressure control offset

General Configuration Administrator

Supported Phases

Set differential used for pressure make-up when pressure drops less than this value (used in Conditioning Dwell via Pressure phase)

General Configuration Administrator

Conditioning Dwell via Pressure

Enable feature to keep air in-bleed open during wash in End Phase

General Configuration Administrator

0

Set wash time delay (for End Phase)

General Configuration Administrator

0

Set N2 inject temperature min/max alarm tolerance

General Configuration Administrator

0

Change pressure increment for specified duration

General Configuration Administrator

Supported Phases

Select Run mode

Junior Operator

Run Command

Select Hold mode

Junior Operator

Hold Command

Select Stop mode

Junior Operator

Stop Command

View IO Status

Maintenance Manager

IO Status

Approve Flammable Cycle Definition

Management

Cycle Definition

 

Approve cycle with the warning: %Air rule was not met

Management

Cycle Definition

Approve cycle with the warning: LEL/Flammability rule was not met

Management

Flammability Pressure Curves

Approve cycle with the warning: pressure curve entered the region between the two flammability curves

Management

Flammability Pressure Curves

Manually control a motor starter

Manual Equipment Controller

Manual

Manually control a proportional valve

Manual Equipment Controller

Manual

Manually control on/off valves

Manual Equipment Controller

Manual

Manually control a device while the area is in Dormant sequence.

Manual_Equipment_Controller.Seq.Dormant

Dormant Sequence

Configure PID loop

PID Loop Configurator

Rate Control

View PLC event configuration

Event Configuration Viewer

Event Configuration

Manage calibration primary standards

Primary Standards Manager

Manual

Sign calibration certificate as “Quality Assurance”

Quality Assurance

Manual

Print current screen to clipboard and to the default printer

Reporter

User Interfaces

Capture the current state of the chamber on the run record

Run Record Generation User

Chamber P&ID Window

Set Manual mode for selected equipment

Senior Operator

Manual

Select and download a load to the chamber for processing

Senior Operator

Loads

Create a new load

Senior Operator

User Interfaces

The I/O status screens will allow the operator to view the diagnostic details. To access this screen, right-click anywhere on the chamber P&ID and select “Show Diagnostics Detail.”

Delete a load from the process controller

Senior Operator

Deleting a Load from the Process Controller

Start a cycle

Senior Operator

Start Command

Abort Cycle

Senior Operator

Abort Command

Set EO drum empty net weight

Senior Operator

0

Set EO stagnant weight amount

Senior Operator

0

Enable/Disable a sensor

Sensor Controller

Chamber P&ID Window

Administer Users

User Administrator

User Management Form

Set feedback delay time for a valve

Valve Feedback Delay Setter

Chamber P&ID Window

View SCADA screens

Viewer

User Interfaces

View Reports

Viewer

NA

Abort Cycle

Abort Cycle

Dormant Sequence

(Force) Clear an Alarm

Force Clear Alarm

0